Conductive systems

conductive

VIASOLESD

The conductive coating system for clean rooms, personal protection and all areas in which ESD requirements have to be satisfied

SYSTEM STRUCTURE


Matt seal (optional)
conductive
VIASOL PU-S648

Conductive top layer
self-levelling, smooth
VIASOL EP-C544

Conductive layer
with copper band wall connection
VIASOL EP-E436

Levelling layer (contingency item)
VIASOL EP-L300 or EP-C500

Adhesive Primer
VIASOL EP-P210

Substrate / concrete

System thickness approx. 2 - 4 mm

SYSTEM INFORMATION

Four-layer epoxy resin floor coating systems

Requirements for conductive floors:
1) Explosion protection: Charges must be directed away safely and QUICKLY
2) Protection of electrostatically sensitive components: Charges must be directed away within given resistance windows
3) Personal protection: Charges must not be directed away too quickly

Requirement / Standard
Required values / measurements
VIASOLSYSTEM
1) Guideline BGR 132
(DIN EN 1081)
Resistance to earth RE = 108 O
(for explosives RE = 106 O)
VIASOLVOLTEX
2) DIN EN 61340-5-1
(replaces DIN EN 100 015)
Resistance to earth RE = 108 O or
floor as primary connection to earth
System resistance (person/shoe/floor)
7,5 x 105 O (750 kO) = RS = 3,5 x 107 O (35 MO)
VIASOLESD
3) ESD STM 97.2 - 1999
(Walking Test)

DIN VDE 0100-410

Electrostatic charging of personnel below 100 V
XYZ

Insulation resistance
RI = 5 x 104 O (nominal plant voltage < 500 V)
RI = 10 x 104 O (nominal plant voltage > 500 V)
VIASOLESD
XYZ

VIASOLESD


SYSTEM BENEFITS

conductive / antistatic
hard-wearing, durable in the context of moderate mechanical loads
good chemical resistance (including diainfectants) and very good resistance to abrasion
smooth surfaces that are easy to clean
easy to decontaminate
resistant to backward moisture penetration
available in a wide range of colours

 

VIASOLUNIVERSAL voltex

The conductive coating system for explosion-proof zones and all areas in wich electrostatic charges must be avoided

SYSTEM STRUCTURE

 

Conductive top layer
self-levelling, smooth
VIASOL EP-C540
or
VIASOL PU-C540

Conductive layer
with copper band wall connection
VIASOL EP-E480

Levelling layer (contingency item)
VIASOL EP-L300

Adhesive primer
VIASOL EP-P210

Substrate / Concrete

System thickness approx. 2 - 4 mm

SYSTEM INFORMATION

Four-layer epoxy resin floor coating systems

Requirements for conductive floors:
1) Explosion protection: Charges must be directed away safely and QUICKLY
2) Protection of electrostatically sensitive components: Charges must be directed away within given resistance windows
3) Personal protection: Charges must not be directed away too quickly

Requirement / Standard
Required values / measurements
VIASOLSYSTEM
1) Guideline BGR 132
(DIN EN 1081)
Resistance to earth RE = 108 O
(for explosives RE = 106 O)
VIASOLVOLTEX
2) DIN EN 61340-5-1
(replaces DIN EN 100 015)
Resistance to earth RE = 108 O or
floor as primary connection to earth
System resistance (person/shoe/floor)
7,5 x 105 O (750 kO) = RS = 3,5 x 107 O (35 MO)
VIASOLESD
3) ESD STM 97.2 - 1999
(Walking Test)

DIN VDE 0100-410

Electrostatic charging of personnel below 100 V
XYZ

Insulation resistance
RI = 5 x 104 O (nominal plant voltage < 500 V)
RI = 10 x 104 O (nominal plant voltage > 500 V)
VIASOLESD
XYZ

VIASOLESD

SYSTEM BENEFITS

conductive / antistatic
hard-wearing, durable in the context of moderate mechanical loads
good chemical resistance (including diainfectants) and very good resistance to abrasion
smooth surfaces that are easy to clean
easy to decontaminate
resistant to backward moisture penetration
available in a wide range of colours

MC Resin Flooring UK & Ireland